|
Lightweight Concrete
INFORMATION SHEET
|
No. 8
Revised 3-87
|

EXPANDED SHALE CLAY AND SLATE INSTITUTE - SALT LAKE CITY, UTAH 84117

SOUND TRANSMISSION PROPERTIES
The control of sound in rooms of buildings may be classified with respect to the origin
of the sound-namely. sounds originating within the room and sounds originating outside the
room. Efficient and economical control of sound is dependent not only upon its origin. but
also upon the design of the enclosure and type of occupancy.
For reduction of sound originating within a room, the sound absorption qualities of the
walls, ceiling and flooring as well as furnishings are important. The type and use of the
room affords the architect latitude in the selection of sound absorption materials for
elements of the room, see Information Sheet #9. Enclosures with high ceilings and large
expanse of wall areas, as in gymnasiums and churches, might utilize sound absorbing
textured masonry walls as an economical solution. On the other hand, for enclosures with
relatively low ceilings. and rather small exposed wall areas, as in offices and
schoolrooms, the use of acoustical ceilings, floor coverings, and interior furnishings
might be the more effective solution.
This information sheet is concerned primarily with the reduction of sound through
concrete and concrete masonry partitions from sources outside of rooms. These sounds are
transmitted as solidborne, as well as air-borne noise. For example. a bare concrete
floor transmits the sound of footsteps between rooms. the sound traveling through the
rigid concrete slab. Solid-borne sound should be suppressed at the source. A concrete
floor for example. should be covered with some type of resilient material. depending upon
the extent of solid-borne sound transmission which should be suppressed.
Air-borne sound may be effectively reduced by barriers such as concrete masonry
partitions. Obviously. attention should be given to doors and their closures. as well as
connections of the walls at the ceilings and floors. Too often the effectiveness of a
concrete masonry partition which should provide satisfactory acoustical isolation is
unnecessarily lost. This may occur by failure to take into account the other important
factors that are involved. such as continuing the partition to the structural ceiling.
Also, cutting of continuous holes through the wall for ducts, electrical outlets, should
be avoided.
Back to top
SOUND ENERGY
Sound energy is measured in decibels. The decibel is a convenient unit because it is
approximately the smallest change in energy that the ear can detect.
The following table of sound intensities will aid in an understanding of decibel
values.
Back to top
TABLE I
|
| Db |
|
| 160 |
Near jet engine |
| 130 |
Threshold of painful sounds; limit of ear's endurance |
| 120 |
Threshold of feeling (varies with frequency) |
| 105 |
Express train passing at high speed. |
| 100 |
Loud automobile horn. 23 feet away |
| 80 |
A subway |
| 70 |
A stenographic room |
| 60 |
Average busy street |
| 55 |
Noisy office or department store |
| 50 |
Moderate restaurant clatter |
| 45 |
Average office |
| 35 |
Soft radio in apartment. The average residence. |
| 20 |
Average whisper four feet away |
| 10 |
Rustle of leaves in gentle breeze |
| 0 |
Threshold of audibility |
|
Back to top
TRANSMISSION
Sound is transmitted through most walls and floors by setting the entire structure into
vibration. This vibration generates new sound waves of reduced intensity on the other
side. The passage of sound into one room of a building from a source located in another
room or outside the building is termed ''sound transmission"
Back to top
TRANSMISSION LOSS
Transmission loss is a measure of the effectiveness of a wall, floor, door or other
barrier in restricting the passage of sound The transmission loss varies with frequency
and the loss is usually greater with higher frequencies. Sound transmission loss
measurements are conducted in accordance with American Society for Testing and Materials
(ASTM) designation E-90. A concrete or concrete masonry wall eleven (11) feet (3.35 m)
wide and nine (9) feet (2.74 m) high mounted on a movable base is rolled between two
isolated reverberation rooms. Measurements are made at 16 frequencies in 1/3 octave bands.
from 125 to 4000 cycles per second. (cps) (generally called Hertz. Hz). The unit of
measure of sound transmission loss is the decibel (dB). The higher the transmission loss
of a wall the better it functions as a barrier to the passage of unwanted noise Back to top
SOUND TRANSMISSION CLASS (STC)
Figure 1
Sound Transmission Class (STC) is a single number rating determined in a prescribed
manner from sound transmission loss values, This rating is arrived at by comparing the
measured transmission losses at the 16 test bands with those of a reference contour having
the form illustrated in Figure 1. The sum of the deficiencies below the contour shall not
be greater than 32 decibels (dB) and the maximum deficiency at a single test point shall
not exceed 8 decibels (dB). When the contour is at the highest value that meets the above
requirements, the Sound Transmission Class for the specimen is the transmission loss (TL)
corresponding to the intersection of the counter and the 500 Hz ordinate. Sound
Transmission Class ratings are established in accordance with ASTM designation E-413,
''Standard Classification for Determination of Sound Transmission Class .' '
This rating provides an estimate of the performance of a partition in sound insulation.
The STC numbers are used to specify the minimum noise insulation needed in a building. For
example, the minimum STC values acceptable for Multi-family housing by the Department of
Housing and Urban Development (HUD) are shown in Table 2 below.
Back to top
|
TABLE 2

|
| HUD SOUND TRANSMISSION REQUIREMENTS FOR WALLS IN MULTIFAMILY HOUSING |
| LOCATION OF PARTITION |
STC |
| Living unit to living unit, corridor(1) or public space, average
noise(2) |
45 |
| Living unit to public space and service areas, high noise(3)(4) |
50 |
|
Notes:
- These values assume floors in corridor are carpeted: otherwise increase STC by 5
- Public space of average noise includes lobbies, storage rooms, stairways, etc.
- Areas of nigh noise include boiler rooms, mechanical equipment rooms, elevator shafts,
laundries. incinerator shafts, garages, and most commercial uses.
- Increase STC by 5 when over or under mechanical equipment which operates at high noise
levels.
|
Many walls constructed with lightweight concrete masonry units produced with expanded
shale, clay or slate by the rotary kiln method have been tested. Tests of these various
walls are listed in Table 3.
The results shown in this table indicate that concrete and concrete masonry produced
with expanded shale clay and slate aggregates meet existing standards.
Back to top
| TABLE 3 SOUND TRANSMISSION CLASS (STC) for LIGHTWEIGHT CONCRETE MASONRY
WALLS |
| MASONRY WALL THICKNESS |
4 inch |
6 inch |
8 inch |
12 inch |
| Plain |
40 |
44 |
45 |
|
| Painted |
41 |
45 |
46 |
50 |
| Wall Board |
47 |
49 |
56 |
|
| Plastered |
50 |
50 |
51 |
|
| Cores Filled with insulation |
|
|
51 |
|
| COMPOSITES*Cavity*Grouted |
|
| 8" |
|
| 4" Block plus 4" Concrete Brick |
|
plain |
51 |
|
|
|
1/2" plastered on block surface |
53 |
|
|
|
1/2" gyp. on block face |
56 |
|
|
| 10" CAVITY |
|
| 4" Block2" Cavity4&#quot; Concrete Brick |
|
plain |
54 |
|
|
|
1/2" plastered on Block |
57 |
|
|
|
1/2" gyp. on block |
59 |
|
| 8" GROUTED BLOCK |
|
All cells grouted |
48 |
|
|
|
1/2" plaster both sides |
56 |
|
|
|
1/2" gyp. both sides |
60 |
|
· The National Concrete Masonry Association was sponsor of the
composites cavity, & grouted walls. Back
to top
IMPACT SOUND
The increased noisiness of our environment has led to increased interest in sound
isolation from impact noise. Impact noise is caused by such things as footsteps. dropped
toys and some appliances. Isolation against impact noise provided by a given floor
construction is measured in accordance with ASTM E492 "Laboratory Measurement of
Impact Sound Transmission Through Floor-Ceiling Assemblies Using The Tapping
Machine." This procedure utilizes a standard tapping machine that is placed in
operation on a test floor specimen which forms a horizontal separation between two rooms,
one directly above the other. The transmitted impact sound is measured in 1/3 octave bands
over a frequency range of 100 to 3150 Hz in the receiving room below. From the data
collected a single figure rating, called Impact Insulation Class (IIC). is derived in a
prescribed manner from the values of the impact sound pressure levels measured in the
receiving room. The rating provides an estimate of the impact sound insulating performance
of a floorceiling assembly. Details of the procedures are outlined in ASTM E492.
The Expanded Shale Clay & Slate Institute sponsored a test program at Riverbank
Laboratories, Geneva, Illinois, to determine the effect of the concrete weight and Modulus
of Elasticity on impact sound transmission. Slab thicknesses of 5 inches and 10 inches
were selected for study. Three concretes designed to weight approximately 95. 115, and 150
pounds per cubic foot were used, so the weight per square foot of floor would cover a
broad range. The slabs were designed for 3000 psi (210 Kgsg. cm.) concrete and included
reinforcement in keeping with flat plate design.
The Impact Noise Reduction (INR) factors determined from the Riverbank Laboratory tests
have been converted to the current designation, Impact Insulation Class (IIC). and are
shown in Table #4.
Comparison of the test data with the current HUD requirements indicated that concrete
floors of any weight require additional surface treatment to bring the IIC rating to
acceptable levels. (see Table 5)
Back to top
| TABLE #4 Impact Insulation Class (IIC) |
| Slab Thickness |
|
5 inch |
|
|
10 inch |
|
| Slab Wt Ibs/cu.ft. |
95 |
115 |
150 |
95 |
115 |
150 |
| IIC Bare Floor |
23 |
24 |
24 |
23 |
30 |
31 |
| IIC Std. Carpet |
|
68 |
|
|
74 |
|
| IIC Vinyl Tile |
|
|
|
|
33 |
|
| Estimated from NRC (National Research Council) report |
| 1/8 inch Vinyl asbestos on 1/2 inch plywood on furring |
|
48 |
48 |
52 |
53 |
|
| Viscose Carpet with 1/8 inch loop pile, coated back |
57 |
58 |
|
62 |
64 |
|
| Impact Insulation Class (IIC) values that are acceptable for multifamily housing under
HUD are listed in Table #5 below. |
|
Back to top
| TABLE #5 HUD Sound Transmission Limitations for Floors in
MultiFamily Housing |
| LOCATION OF FLOORCEILING |
STC |
IIC |
| Floor-ceiling separating living units from other living units, public space (1) or
service areas (2) |
45 |
45 |
| Floor-ceiling separating living units from public space and service areas (high noise)
(3) including corridor floors over living units |
50 |
50 |
Note: (1) Does not apply to door above storage rooms where noise from
living units would not be objectionable.
(2) Public space of average noise includes lobbies, storage rooms, stairways, etc.
(3) Areas or high noise include boiler rooms, mechanical equipment rooms, elevator shafts,
laundries, incinerator shafts, garages and most commercial uses. |
Back to top
CONCLUSION
Expanded Shale Clay & Slate aggregate concrete and concrete masonry meets the
commonly accepted specification for air borne noise reduction. This quality combined with
its demonstrated durability. Fire resistance, thermal insulation properties and aesthetics
quality make it an extremely desirable and practical building material.
Back to top
References:
Expanded Shale Clay & Slate Institute.
1. Lightweight Concrete Information Sheet No. 9. "Sound Absorption of Concrete
Masonry Walls."
National Concrete Masonry Association.
- TEK Sheet #9. "Estimating Sound Transmission Class of Concrete Masonry."
- TEK Sheet $#18. "Noise Control with Concrete Masonry in MultiFamily Housing."
- TEK Sheet #69. "Noise Insulation with Concrete Masonry."
- TEK Sheet #69.A, "New Data on Sound Reduction with Concrete Masonry Walls.''
Building Materials and Structures Report 144. National Bureau of Standards.
''Insulating Concretes". by R.C. Valore, Jr.. ACI Journal November. 1956.
''Impact Sound Transmission Tests On A Concrete Slab Floor with Various Surface
Constructions" by D. Olynyk. Division of Building Research. National Research
Council. Ottawa. Canada. July. 1967.
EXPANDED SHALE CLAY AND SLATE INSTITUTESALT LAKE CITY, UTAH 84117
COPYRIGHT, 1966, EXPANDED SHALE, CLAY AND SLATE INSTITUTE
Back to top
Sound Absorption
Three terms are introduced to define and evaluate sound absorption. These are the Sound
Absorption Coefficient, Sabin, and Noise Reduction Coefficient. The Sound Absorption
Coefficient is a measure of the proportion of the sound striking a surface which is
absorbed by that surface, and is usually given for a particular frequency. Thus, a surface
which would absorb 100% of the incident sound would have a Sound Absorption Coefficient of
1.00, while a surface which absorbs 45% of the sound, and reflects 55% of it, would have a
Sound Absorption Coefficient of 0.45. A Sabin or square-foot Unit of Absorption is defined
as the amount of sound absorbed by one square foot of surface having a Sound Absorption
Coefficient of 1.00. The number of Sabins (Absorption Units) of a given area is then the
product of the area and the Sound Absorption Coefficient. 100 sq. ft. of a surface with a
Sound Absorption Coefficient of 0.25 furnishes 25 Sabins (Absorption Units). Most
materials are tested at frequencies from 125 to 4000 cycles per second (cps) in octave
steps. The Noise Reduction Coefficient is the average of the Sound Absorption Coefficient
at 250,000, 1000 and 2000 cps in octave steps. The Table lists approximate values of the
Noise Reduction Coefficients of numerous materials.
Back to top
Noise Reduction Coefficients
| Material |
Approx. N.R.C. |
|
| Expanded Shale Block, Medium Texture, unpainted |
0.45 |
Add 10% for Coarse Texture, Deduct 10% for Fine Texture |
| Heavy Aggregate Block, Medium Texture, unpainted |
0.27 |
Add 5% for Coarse Texture, Deduct 5% for Fine Texture |
| DEDUCTIONS FROM ABOVE FOR PAINTED BLOCK |
| PAINT TYPE |
APPLICATION |
ONE COAT |
TWO COATS |
THREE COATS |
| Any |
Spray |
10% |
20% |
70% |
| Oil Base |
Brushed |
20 |
55 |
75 |
| Latex or Resin Base |
Brushed |
30 |
55 |
90 |
| Cement Base |
Brushed |
60 |
90 |
|
| Material |
N.R.C. |
| Brick Wallunpainted |
.05 |
| painted |
.02 |
| Floors |
| Concrete or terrazzo |
.02 |
| Wood |
.03 |
| Linoleum, asphalt, rubber or cork tile on concrete |
.03-.08 |
| Glass |
.02 |
| Marble or glazed tile |
.01 |
| Plaster, gypsum or lime, smooth finish on tile or brick |
.04 |
| Same, on lath |
.04 |
| Plaster, gypsum or lime, rough finish on lath |
.05 |
| Plaster, acoustical |
.21 |
| Wood paneling |
.06 |
| Acoustical ceiling tile |
.55-.85 |
| Carpet, heavy, on concrete |
.45 |
| Carpet, heavy, hairfelt underlay |
.70 |
| Fabrics |
| Light, 10 oz. per sq. yd. hung straight |
.20 |
| Medium, 14 oz. per sq. yd. draped to half area |
.57 |
| Heavy, 18 oz. per sq. yd. draped to half area |
.63 |
| Audience, seated, depending on character of seats, spacing, etc |
3.0-6.0 |
| Chairs, metal or wood |
.20 |
| Wood pews |
.40 |
| Same with cushions |
2.00 |
| Theatre and auditorium chairs |
| Wood veneer seat and back |
.50 |
| Upholstered in leatherette |
2.10 |
| Heavily upholstered in plush or mohair |
3.0-3.5 |
| Openings |
| Stage, depending on furnishings |
.25-.75 |
| Deep balcony, upholstered seats |
.50-1.00 |
| Grills, ventilating |
.15-.50 |
Back to top
Sound Transmission
The architect in considering the reduction of sound through walls separating rooms of
schools, hotels, or office buildings for example, is concerned with reducing a sound
intensity of say, 55 decibels to something on the order of 15 decibels or less. He is able
to select these values by referring to the Table. Referring to the chart and the curve
representing an expanded shale masonry unit with an 8" x 16" face, it is found
that a unit weighing 15 Ibs. air dried, will offer a transmission loss of approximately 42
decibels (if properly sealed). The average 4-8-16 expanded shale masonry unit weighs
approximately 15 Ibs. air dried, therefore a partition wall made of these units can be
expected to reduce the sound transmission satisfactorily for the assumed situation,
provided of course, the surfaces of the wall are sealed sufficiently to prevent the direct
passage of sound through the voids.
Back to top
Masonry vs. Steel Stud
Because the sound-diminishing qualities of concrete masonry 'keep the noise outside',
structures utilizing the masonry backup system enjoy a quieter internal environment. In
contrast, the dry wall component of the steel stud system frequently contains acoustical
holes. This negative factor is substantially magnified when we consider the fact that the
steel stud system, itself, is inherently noisy. The mass and monolithic properties of
concrete masonry make the system far superior in its ability to reduce sound transmission.
Back to top
Copyright 1998, Norlite Corporation, all rights reserved.
|